| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not properly handle URIs beginning with a 0xfa character, which allows remote attackers to read data from arbitrary memory locations or cause a denial of service (application crash) via a crafted POST request. |
| Multiple cross-site scripting (XSS) vulnerabilities in the HMI web application in Siemens WinCC (TIA Portal) 11 allow remote attackers to inject arbitrary web script or HTML via a crafted URL. |
| Directory traversal vulnerability in Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to read arbitrary files via crafted packets to TCP port 4999. |
| Siemens RuggedCom Rugged Operating System (ROS) before 3.12, ROX I OS through 1.14.5, ROX II OS through 2.3.0, and RuggedMax OS through 4.2.1.4621.22 use hardcoded private keys for SSL and SSH communication, which makes it easier for man-in-the-middle attackers to spoof servers and decrypt network traffic by leveraging the availability of these keys within ROS files at all customer installations. |
| Absolute path traversal vulnerability in the ALMListView.ALMListCtrl ActiveX control in almaxcx.dll in the graphical user interface in Siemens Automation License Manager (ALM) 2.0 through 5.1+SP1+Upd2 allows remote attackers to overwrite arbitrary files via the Save method. |
| RuggedCom Rugged Operating System (ROS) 3.10.x and earlier has a factory account with a password derived from the MAC Address field in the banner, which makes it easier for remote attackers to obtain access by performing a calculation on this address value, and then establishing a (1) TELNET, (2) remote shell (aka rsh), or (3) serial-console session. |
| The integrated web server in Siemens SIMATIC WinCC OA before 3.12 P002 January allows remote attackers to execute arbitrary code via crafted packets to TCP port 4999. |
| The SNMP implementation in Siemens RuggedCom ROS before 3.11, ROS 3.11 for RS950G, ROS 3.12 before 3.12.4, and ROS 4.0 for RSG2488 allows remote attackers to cause a denial of service (device outage) via crafted packets. |
| The integrated HTTPS server in Siemens RuggedCom ROS before 3.12.2 allows remote attackers to hijack web sessions by predicting a session id value. |
| Cross-site scripting (XSS) vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to inject arbitrary web script or HTML via unspecified data. |
| An unspecified ActiveX control in ActBar.ocx in Siemens Tecnomatix FactoryLink 6.6.1 (aka 6.6 SP1), 7.5.217 (aka 7.5 SP2), and 8.0.2.54 allows remote attackers to create or overwrite arbitrary files via the save method. |
| The integrated web server on Siemens SCALANCE X-200 switches with firmware before 4.5.0 and X-200IRT switches with firmware before 5.1.0 does not properly enforce authentication requirements, which allows remote attackers to perform administrative actions via requests to the management interface. |
| Open redirect vulnerability in Siemens WinCC (TIA Portal) 11 and 12 before 12 SP1 allows remote attackers to redirect users to arbitrary web sites and conduct phishing attacks by leveraging improper configuration of SIMATIC HMI panels by the WinCC product. |
| Cross-site request forgery (CSRF) vulnerability in Siemens WinCC (TIA Portal) 11 and 12 before 12 SP1 allows remote attackers to hijack the authentication of unspecified victims by leveraging improper configuration of SIMATIC HMI panels by the WinCC product. |
| core/getLog.php on the Siemens Enterprise OpenScape Branch appliance and OpenScape Session Border Controller (SBC) before 2 R0.32.0, and 7 before 7 R1.7.0, allows remote attackers to obtain sensitive server and statistics information via unspecified vectors. |
| The login implementation in the Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, has a hardcoded account, which makes it easier for remote attackers to obtain access via an unspecified request. |
| Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, does not properly assign privileges for the database containing WebNavigator credentials, which allows remote authenticated users to obtain sensitive information via a SQL query. |
| Cross-site scripting (XSS) vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to inject arbitrary web script or HTML via unspecified vectors, a different vulnerability than CVE-2011-4510. |
| Cross-site scripting (XSS) vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to inject arbitrary web script or HTML via unspecified vectors, a different vulnerability than CVE-2011-4511. |
| The HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime has an improperly selected default password for the administrator account, which makes it easier for remote attackers to obtain access via a brute-force approach involving many HTTP requests. |