| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| SQL injection vulnerability in the login screen in the Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, allows remote attackers to execute arbitrary SQL commands via unspecified vectors. |
| Unspecified vulnerability in the client library in Siemens COMOS 9.2 before 9.2.0.6.10 and 10.0 before 10.0.3.0.4 allows local users to obtain unintended write access to the database by leveraging read access. |
| Siemens Simatic WinCC and PCS 7 SCADA system uses a hard-coded password, which allows local users to access a back-end database and gain privileges, as demonstrated in the wild in July 2010 by the Stuxnet worm, a different vulnerability than CVE-2010-2568. |
| The HMI web application in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to cause a denial of service (daemon crash) via a crafted HTTP request. |
| CRLF injection vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote attackers to inject arbitrary HTTP headers and conduct HTTP response splitting attacks via a crafted URL. |
| Unspecified vulnerability in the command-line management interface on Siemens Scalance W7xx devices with firmware before 4.5.4 allows remote attackers to bypass authentication and execute arbitrary code via a (1) SSH or (2) TELNET connection. |
| Directory traversal vulnerability in the web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote authenticated users to read arbitrary files via vectors involving a query for a pathname. |
| The Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, exhibits different behavior for NetBIOS user names depending on whether the user account exists, which allows remote authenticated users to enumerate account names via crafted URL parameters. |
| Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, does not properly represent WebNavigator credentials in a database, which makes it easier for remote authenticated users to obtain sensitive information via a SQL query. |
| Directory traversal vulnerability in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to read HMI web-application source code and user-defined scripts via a crafted URL. |
| HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to cause a denial of service (application crash) by sending crafted data over TCP. |
| Multiple buffer overflows in Siemens Automation License Manager (ALM) 4.0 through 5.1+SP1+Upd1 allow remote attackers to execute arbitrary code via a long serialid field in an _licensekey command, as demonstrated by the (1) check_licensekey or (2) read_licensekey command. |
| The HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime has an improperly selected default password for the administrator account, which makes it easier for remote attackers to obtain access via a brute-force approach involving many HTTP requests. |
| Cross-site scripting (XSS) vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to inject arbitrary web script or HTML via unspecified vectors, a different vulnerability than CVE-2011-4511. |
| Cross-site scripting (XSS) vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote attackers to inject arbitrary web script or HTML via a crafted URL. |
| The client application in Siemens COMOS before 9.1 Update 458, 9.2 before 9.2.0.6.37, and 10.0 before 10.0.3.0.19 allows local users to gain privileges and bypass intended database-operation restrictions by leveraging COMOS project access. |
| The integrated web server on Siemens SCALANCE X-200 switches with firmware before 4.5.0 and X-200IRT switches with firmware before 5.1.0 does not properly enforce authentication requirements, which allows remote attackers to perform administrative actions via requests to the management interface. |
| The debugging feature on the Siemens CP 1604 and CP 1616 interface cards with firmware before 2.5.2 allows remote attackers to execute arbitrary code via a crafted packet to UDP port 17185. |
| Buffer overflow in a third-party ActiveX component in Siemens SIMATIC RF-MANAGER 2008, and RF-MANAGER Basic 3.0 and earlier, allows remote attackers to execute arbitrary code via a crafted web site. |
| Directory traversal vulnerability in HmiLoad in the runtime loader in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime, when Transfer Mode is enabled, allows remote attackers to execute, read, create, modify, or delete arbitrary files via a .. (dot dot) in a string. |